Talk with one of our sales
Monday to Friday 8AM - 5PM WIB
021- 72791867
The new flue gas analyzer testo 310 combines simple functions with a high level of masurement accuracy, and is therefore perfectly suited to all basic measurements on a heating system. Long battery lifetimes of up to ten hours guarantee high availability. Its easy handling and compact design make the testo 310 a robust tool for day-to-day work – even when things get rough. Clear reports can be created as required on site thanks to the infrared interface printer specially developed for the testo 310. The current measurement value can be printed out from all measurement menus, either during or after the measurement. The testo 310 offers all avantages of electronic flue gas measurement in high quality at a perfect cost/benefit ratio.
Accessories
Product sets Part no.
testo 310 flue gas set |
0563 3100 |
testo 310 flue gas set with printer |
0563 3110 |
Accessories for measuring instrument
USB mains unit incl. cable |
0554 1105 |
Testo IR printer |
0554 3100 |
Testo fast printer IRDA |
0554 0549 |
Spare thermal paper for printer, permanent ink |
0554 0568 |
Spare particle filter |
0554 0040 |
Spare gas sensors
Replacement O2 sensor |
0390 0085 |
Spare CO sensor |
0390 0119 |
Technical Data
Measuring range Accuracy +1 digit Resolution Adjustment time t90
Temperature (flue gas) |
0 to +400 °C |
±1 °C (0 to +100 °C) ±1.5% of m.v. (>100 °C) |
0.1 °C |
kurang dari 50 s |
Temperature (ambient temperature) |
-20 to +100.0 °C |
±1 °C |
0.1 °C |
kurang dari 50 s |
Draught measurement |
-20 to +20 hPa |
±0.03 hPa (-3.00 to +3.00 hPa) ±1.5% of m.v. (remaining range) |
0.01 hPa |
|
Pressure measurement |
-40 to 40 hPa |
±0.5 hPa |
0.1 hPa |
|
O2 measurement |
0 to 21 Vol. % |
±0.2 Vol. % |
0.1 Vol. % |
30 s |
CO measurement (without H2 compensation) |
0 to 4000 ppm |
±20 ppm (0 to 400 ppm) ±5% of m.v. (401 to 2000 ppm) ±10% of m.v. (2001 to 4000 ppm) |
1 ppm |
60 s |
Ambient CO measurement |
0 to 4000 ppm |
±20 ppm (0 to 400 ppm) ±5% of m.v. (401 to 2000 ppm) ±10% of m.v. (2001 to 4000 ppm) |
1 ppm |
60 s |
Efficiency (ETA) |
0 to 120 % |
- |
0.1% |
- |
Flue gas loss |
0 to 99.9% |
- |
0.1% |
- |
General Technical Data
Storage temperature |
-20 to +50 °C |
Operating temperature |
-5 to +45 °C |
Power supply |
Battery: 1500 mAh, mains unit 5V/1A |
Memory |
No memory |
Display |
Backlit 2-line display |
Weight with probe |
Approx. 700 g |
Dimensions |
201 x 83 x 44 mm |